R-404A is a long-standing commercial refrigeration blend — supermarket racks, walk-in coolers and freezers, cold storage and refrigerated transport. Its GWP of 3,922 is nearly twice R-410A's, which is why the Technology Transitions rule keeps it out of most new refrigeration equipment. From January 1, 2026, an R-404A appliance with a full charge of 15 lbs or more is covered by the Subpart C leak-repair rule: a leak-rate calculation when refrigerant is added, against a 20% threshold for retail food and cold storage refrigeration and 10% for refrigerated transport. A unit under 15 lbs is outside § 84.106(a).

GWP (40 CFR 84.64)

3,922

Safety Class

A1

ODP

0

Composition

R-125 / R-143a / R-134a (44/52/4)

Calculate Your R-404A Leak Rate

Equipment Setup

R-404A

Typical range: Under 15 lbs (self-contained units) to 1,000+ lbs (supermarket racks, cold storage)

Log Refrigerant Addition

Enter every addition, including a charge added right after an installation or a retrofit or a seasonal-variance re-addition (no more than was removed in the prior change in season, both within one consecutive 12-month period; EPA has read any amount above that as a leak, 81 FR 82322): its date is where the next annualizing count starts. Those charges need no leak-rate calculation of their own and don't count toward 125% (§ 84.106(b), (j)), but this calculator counts every addition you enter, so its figures run high when one is included. Ref LeakLog marks them excluded and keeps the date.

Annualizing Method

rate = (lbs_added ÷ full_charge) × (365 ÷ D) × 100

Where D = days since the previous addition, capped at 365 (365 when no earlier addition is entered). Projects a single addition over a full year. For an appliance's first calculation after January 1, 2026, § 84.106(b)(1) substitutes 365 days for D, which EPA allows only when previous records are absent (89 FR 82724).

R-404A leak rate (annualizing)

—

ADD R-404A SERVICE EVENTS TO CALCULATE

Commercial Refrigeration · 20% EPA threshold

365-Day Total

0.0 lbs

Chronic Leaker

0%

of 125% threshold

Events

0

R-404A Service Events

No service events yet.

Enter an R-404A addition above to see your EPA-compliant leak rate calculation in real time.

Track R-404A Compliance Automatically

Stop calculating by hand. Ref LeakLog automates R-404A leak rate tracking, repair workflows, audit-ready reports, and team management for the 2026 mandate.

Start Your 14-Day Free Trial

R-404A Compliance Under the 2026 Rule

From January 1, 2026, R-404A appliances with a full charge of 15 lbs or more are covered by the Subpart C leak-repair rule (§ 84.106(a)); smaller units are outside it

Leak rate thresholds: 20% for commercial refrigeration — retail food and cold storage (§ 84.102) — 30% for industrial process refrigeration, and 10% for refrigerated transport and other appliances (§ 84.106(c)(2))

A rate over the threshold starts a 30-day clock (120 days with an industrial process shutdown) to repair the leaks and pass an initial verification test, followed by a follow-up verification test (§ 84.106(d), (e))

Commercial refrigeration appliances of 500 lbs or more that exceeded the rate get quarterly leak inspections until four quarters in a row stay under it; 15 to under 500 lbs, annual inspections until a year under it (§ 84.106(g)(1))

Chronic-leaker reporting: a covered appliance that leaks 125% or more of its full charge in a calendar year must be reported to EPA by March 1 of the following year (§ 84.106(j))

Technology Transitions: no R-404A in new stand-alone retail food units, vending machines or road and marine transport units (2025), new cold storage warehouse systems, retail food remote condensing units or intermodal containers (July 27, 2026), or new supermarket systems (January 1, 2027); new ice machines from 2026–2027 by type (§ 84.54(a)(4)–(8), (c)(7)–(9), (c)(11)–(12), (c)(14))

Regulatory Status

HFC blend with a GWP of 3,922 — nearly twice R-410A's 2,088. Its HFCs count against the AIM Act production and consumption phasedown (§ 84.7), and the Technology Transitions rule keeps it out of most new commercial refrigeration equipment (§ 84.54).

Under 40 CFR 84.54, R-404A can't go into new stand-alone retail food units or vending machines (GWP limit 150, manufacture or import, since January 1, 2025), new road or marine refrigerated transport (named outright, since January 1, 2025), new intermodal containers with a box temperature of −35 °C or higher (GWP limit 700, since July 27, 2026), new cold storage warehouse systems (GWP limit 700, installation, since July 27, 2026), new retail food remote condensing units (GWP limit 1,400, installation, since July 27, 2026) or new supermarket systems (GWP limit 1,400, from January 1, 2027), and new ice machines are restricted from January 1, 2026 or 2027 depending on type (§ 84.54(a)(8), (c)(14)). An approved building permit issued before October 5, 2023 that specifies the restricted refrigerant for the system pushes the supermarket and cold storage dates back a year (§ 84.54(d)). Existing systems can still be serviced; from January 1, 2029, supermarket systems, refrigerated transport and automatic commercial ice makers must be serviced with reclaimed refrigerant (§ 84.112(e)).

Common Applications

  • Supermarket display cases
  • Walk-in coolers and freezers
  • Refrigerated transport
  • Cold storage warehouses
  • Commercial ice machines

Frequently Asked Questions

What is the EPA leak rate threshold for R-404A commercial refrigeration?

20%. Commercial refrigeration under § 84.102 means the retail food and cold storage subsectors — supermarkets, convenience stores, restaurants and other food service establishments, and cold storage warehouses — and its threshold is 20% (40 CFR 84.106(c)(2)(i)). Refrigerated transport and refrigeration outside those subsectors are 10%, and industrial process refrigeration is 30% (§ 84.106(c)(2)(ii)–(iii)). The rule applies to appliances with a full charge of 15 lbs or more. A rate over the threshold means repairing the leaks and passing an initial verification test within 30 days of the addition (120 days with an industrial process shutdown), then a follow-up verification test (§ 84.106(d)–(e)).

Why does R-404A's GWP matter for compliance?

R-404A's GWP is 3,922 — the mass-weighted sum of its HFCs' exchange values (40 CFR 84.64(b) and appendix A: 44% HFC-125 at 3,500, 52% HFC-143a at 4,470, 4% HFC-134a at 1,430) — nearly twice R-410A's 2,088. That number is why the Technology Transitions rule bars it from most new refrigeration equipment: the GWP limits for new retail food, cold storage and transport systems run from 150 to 1,400, and R-404A is named outright in the transport and ice machine rows (§ 84.54). The leak-repair thresholds don't depend on GWP, though: a covered R-404A rack has the same 20% rate as any other commercial refrigeration appliance.

Can I still use R-404A in existing systems?

Yes. The Technology Transitions rule restricts R-404A in new products and newly installed systems (§ 84.54); servicing an existing system is still allowed — but work that adds cooling capacity (more than 15% for a supermarket system, any increase for other systems) or replaces 75% or more of the evaporators and all of the racks, condensers and connected loads counts as a new installation (§ 84.54(e)). Two dates to plan around: from January 1, 2029, supermarket systems, refrigerated transport and automatic commercial ice makers that contain an HFC must be serviced with reclaimed refrigerant (§ 84.112(e)), and the AIM Act cap on new HFC production and consumption drops from 60% of baseline to 30% the same year (§ 84.7). Lower-GWP blends such as R-448A and R-449A are sold as R-404A replacements for new and retrofit use.

How do supermarkets track R-404A leak rates?

Each refrigerant-containing appliance with a full charge of 15 lbs or more gets its own leak-rate record, and where a system has more than one independent circuit, each independent circuit is a separate appliance (§ 84.102). A leak rate is calculated when refrigerant is added (§ 84.106(b)), using one method — annualizing or rolling average — for every covered appliance at the facility (§ 84.102). Commercial refrigeration appliances of 1,500 lbs or more installed since January 1, 2017 also need automatic leak detection: at installation or within 30 days for systems installed from January 1, 2026, and by January 1, 2027 for those installed from 2017 through 2025 (§ 84.108(b)). Tracking software keeps that per-appliance record straight.

What is the chronic leaker rule for R-404A systems?

If a covered R-404A appliance leaks 125% or more of its full charge in a calendar year, its owner or operator must report it to EPA by March 1 of the following year (40 CFR 84.106(j)). The measure is refrigerant leaked: in practice, the refrigerant added to replace leaks — not a charge added right after an installation or a retrofit, not a seasonal-variance re-addition, and not purged refrigerant destroyed at 98% or better (§ 84.106(b), (k)).

Don't Calculate By Hand

Ref LeakLog automates R-404A leak rate tracking for your entire fleet — calculations, repair workflows, deadline reminders, and audit-ready PDF reports. The rule has been in effect since January 1, 2026.